MEDIUM PRESSURE CENTRIFUGAL FAN WITH FORWARD IMPELLER
MANUFACTURING FEATURES:
• Rolling steel sheet housing.
• Completely joined or welded housing.
• Galvanised steel sheet simple inlet forward curved impeller.
• Polyester powder finishing coat.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230V 60Hz in single phase motors and 230/400-460V 60Hz in three phase motors.
• Available positions (to be indicated in case of order): LG270, LG0, LG45, LG90, LG135, LG180, LG225, LG315, RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315.
• The indicated codes correspond to the model in position LG270
APPLICATIONS:
Designed for inline installation, they are suitable for:
• Industrial applications, extraction or injection of air.
• Cooling of machines and parts.
• Suitable for transporting totally clean air without dust.
• Maximum working temperature: carried air: 130ºC, environment single phase 50ºC, three phase 60ºC.
UNDER REQUEST:
• Special voltages.
• 2 speed motors (three phase motors).
•Fan for air working temperatures up to 250ºC.
• Fans provided with cooling disk for high temperature.
• Option with support for models where it is not included, and without support for models where it is included.
A | B | C | D | E | F | G | H | K | N | O | P | Q | S | TØ | UØ | VØ |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
364 | 321 | 141 | 142 | 210 | 105 | 101,5 | 333 | 230 | 128 | 134 | 159 | 255 | 153 | 9 | 161 | 9 |
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
MANUFACTURING FRATURES
• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of galvanised steel models 7,9, 10, 12 and 15. And the rest of models with polyester powder finishing coat.
MANUFACTURING FEATURES
• Connection to be fitted in the centrifugal fans outlet.
• Manufactured in galvanized steel.
UNDER REQUEST
• Versions in stainless 304 and stainless 316.
MANUFACTURING FEATURES
• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.
MANUFACTURING FEATURES
• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.
MANUFACTURING FRATURES
• Outlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of steel and protected against corrosion with polyester resin powder.
Structure made of extruded aluminum profiles available in different dimensions according to the panel to be installed and the fan volume. The profiles joining is made of polyamide corners, which gives them great strength and the possibility of disassembling the structure into pieces.
Panels can be made of a single sheet with inner insulation of 10 mm thick polyethylene foam, or 2 sheets (sandwich panel) with thicknesses of 25 mm or 50 mm, depending on the required attenuation degree.
The sheets of each panel can be galvanized steel, galvanized steel with coloured plastic coating or stainless steel.
The lower part is finished off with a structure / plinth for transport and handling, made of galvanized sheet or upn-80/100 joist, depending on the cabin dimensions and weight.
The air inlets and outlets of the cabin have anti-vibration tarpaulins coupled to mounted fans. These fans rest on a floating base with acoustic dampers.
RRP to consult.
Nº | Code | Family | Name | Qty |
---|---|---|---|---|
2 | R-253191681 | INLET CONE | MB20/6-20/8 | x1 |
4 | R-253249421 | CASING | MB 20/6 | x1 |