VENTILATION BOX WITH BACKWARD IMPELLER
MANUFACTURING FEATURES:
APPLICATIONS:
Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction.
• Maximum working temperature: three phase 60ºC.
A | B | C | D | E | F | G | H | I |
---|---|---|---|---|---|---|---|---|
940 | 940 | 1007 | 558 | 940 | 47 | 630 | 880 | 1052 |
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
MANUFACTURING FEATURES
• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.
*Dial panel incorporated. Optional EMC filter.
Certifications: CE/UL/CSA/EN/GOST/CCC.
Protection index IP20.
The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.
SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current
MANUFACTURING FEATURES
• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.
*Dial panel incorporated. Optional EMC filter.
Certifications: CE/UL/CSA/EN/GOST/CCC.
Protection index IP20.
The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.
SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current
MANUFACTURING FEATURES
• Allows customization of outlet’s position and shape.
• Made of galvanized steel.
MANUFACTURING FEATURES
• Allows duct connection.
• Made of galvanized steel.
MANUFACTURING FEATURES
• Structure in aluminum profile 30mm, nylon corners, galvanized sandwich panels with internal insulation rockwool (25mm thickness) class A1 (non-combustible) of 90kg/m3 density
• All panels are equipped with "fastening system" for the quick assembly and disassembly whenever required, either for cleaning, maintenance or exchanging of panels.
• Box is supplied without filters.
(Check the filter units needed for the drawer surface, BOX FILTER for KENTALBOX PLUS need 2 filter of each granulometry)
Filter cells for rough primary filtration for air treatment units or air intake grids.
• Thick synthetic media with high retention capacity pleated between 2 rigid screens.
• Large filter surface.
• Frame: galvanised,
• Maximum continuous operating temperature: 70°C
• Relative humidity: 100%
• Tested for food contact according to EC 1935/2004
Filtration for air treatment units equipped with a pre-filter upstream, and air-conditioning units.
• High filtration area, high efficiency, compact and economic filter.
• Media: Mini pleat fiberglass paper
• Frame: Galvanized steel
• Maximum T° in continuous service: 100°C
• Humidity: 100% RH
• Tested for food contact according to CE 1935/2004
• Certified for microbial development (ISO 846-VD 6022)
Filtration for air treatment units equipped with a pre-filter upstream, and air-conditioning units.
• High filtration area, high efficiency, compact and economic filter.
• Media: Mini pleat fiberglass paper
• Frame: Galvanized steel
• Maximum T° in continuous service: 100°C
• Humidity: 100% RH
• Tested for food contact according to CE 1935/2004
• Certified for microbial development (ISO 846-VD 6022)
Nº | Code | Family | Name | Qty |
---|---|---|---|---|
1 | 721001144WEG6 | MOTOR | 0,75kW T6 B5 230/400V 60Hz | x1 |
2 | R-R63D1L500-24 | TURBINE | R63D1L500x140x24 LG | x1 |
3 | R-BAD500PK1 | INLET CONE | ED11P 500 | x1 |