fan image
Model
CLIBOS 561 T6 1,5kW
Code
CD5616106LGRRA1

CLIBOS 561 T6 1,5kW

BACKWARD CENTRIFUGAL PLUG FAN TYPE, DIRECT DRIVEN,  FOR RECIRCULATION OF HOT GASES

MANUFACTURING FEATURES:
• Direct driven centrifugal medium pressure fan, type plug fan.
• Insulated casing made of carbon laminated steel, protected against corrosion by powder polyester coat. Finish C3.
• Thermal insulation with high density rock wool, 145Kg/m3, thickness 50mm
• Self-cleaning and reinforced impeller with high performance backward (reaction) blades made of carbon laminated steel dynamically balanced to minimize noise and vibrations painted In black heat-resistant paint coating.
• Motor for continuous operation (S1) Squirrel cage standardized asynchronous IEC motor with IP-55 protection and Class F electrical insulation. Standard voltages 230/400V 60Hz for three phase motors Up to 4kW and 400/690V 60Hz for higher powers.
• Motor with flange (B5).
• Maximum continuous working temperature ambient (motor): 60ºC.
• Suitable for transferring gases from -40ºC to 250ºC in continuous.
• Integrated cooling impeller

APPLICATIONS:
Plug-type installation made for the recirculation of gases in:
⦁ Ovens
⦁ Boilers
⦁ Paint booths
⦁ Drying of tobacco, barley, ceramic, glass and wood leaves
⦁ Insulated thermal cameras subjected to temperature control
⦁ Burners and incinerators
⦁ Melting furnaces

ON DEMAND:
⦁ Fans for special voltages
⦁ 2 Speed motor, Inox 304 or Inox 316
⦁ Sparking proof construction
⦁ Other sizes
⦁ Other motors according to customer requeriment

Fan

Max flow
10050 m³/h
Weight
160.5 Kg

Motor

Power
1,5 kW
RPM Motor
1128
I max. 230 V
6,45
I max. 400 V
3,71
Size
100L
Weight
28 Kg
Efficiency
86.8 %
FP
0.73
CLIBOS 561 T6 1,5kW
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

CLIBOS 561 T6 1,5kW

Dimensions scheme
±B A C D E F G H
695.6 801 723 399 150 160 192 271.5

CLIBOS 561 T6 1,5kW

Electrical scheme

CLIBOS 561 T6 1,5kW

Model
INT 25 3P A
Code
INT253PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
CLBI 56
Code
BAD-N56-A5
Information
INLET CONE FOR PLUG FANS IN CABINET

MANUFACTURING FEATURES

• Inlet cone for CLIBOS-TR, CLIBOS, CIKSTORM made of carbon steel and protected against corrosion by powder coating polyester resin RAL5010.

Model
CLBC 562 LG
Code
CLBC56-A5
Information
SCROLL FOR PLUG FANS

MANUFACTURING FEATURES

• Scroll for CLIBOS-TR, CLIBOS, CIKSTORM made of carbon steel and painted with anti-heat black paint

Model
SFC 230 I 7A *
Code
SFC230I007
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
SFC 400 III 5A *
Code
SFC400III5
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

CLIBOS 561 T6 1,5kW

Spare parts scheme
Code Family Name Qty
2 R-CTB-CD561-28ALGRR TURBINE CLIBOS-D+RR 561 D28 LG x1