AXIAL FAN 300ºC/2h AND ATEX
MANUFACTURING FEATURES
• Axial fan with circular reinforced frame.
• Modular motor-impeller assembly.
• Cast aluminium impeller with variable pitch angle. Polyester powder finishing coat.
• Standard asynchronous squirrel cage motor with IP-55 protection and Class H insulation certified 300ºC/2h and ATEX (II3G) . Standard voltages 400V(Y) 60Hz in three phase motors up to 3kW and 400V 60Hz for higher powers and 2 speed motors.
APPLICATIONS
Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area and high pressures needed.
• Maximum working temperature: 60ºC.
UNDER REQUEST
• B Form impeller (air flow from impeller to motor).
• 100% reversible impeller.
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2402
C (MOT. 100-112-132) | C (MOT. 160M) | E | O | ØA | ØB | ØDint | ØI |
---|---|---|---|---|---|---|---|
658 | 721 | 340 | 16x22,5º | 1000 | 970 | 903,5 | 12 |
MANUFACTURING FEATURES
• Square support frame for HB fans.
• Made of steel and protected against corrosion with polyester resin powder.
MANUFACTURING FEATURES
• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
Switch for ATEX environments. Suitable for zones 1-2 (gas) and 21-22 (dust), index protection IP65. Manufactured in aluminum alloy and RAL 7000 gray finishing coat. External screws in stainless steel. Control on the front. Tensions up to 690V. According to directive 2014/34 / UE (ATEX).
MANUFACTURING FRATURES
• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.
UNDER REQUEST
• Stainless guard 304 or 316 with electro-polished finishing coat.