Axial fan 400ºC/2h
MANUFACTURING FEATURES
• Axial fan with circular reinforced frame.
• Modular motor-impeller assembly.
• Cast aluminium impeller with variable pitch angle. Polyester powder finishing coat.
• Standard asynchronous squirrel cage motor with IP-55 protection and Class H insulation certified 400ºC/2h and ATEX (II3G). Standard voltages 400V(Y) 60Hz in three phase motors up to 3kW and 400V 60Hz for higher powers and 2 speed motors.
APPLICATIONS
Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area and high pressures needed.
• Maximum working temperature: 60ºC.
UNDER REQUEST
• B Form impeller (air flow from impeller to motor).
• 100% reversible impeller.
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-0914
C (MOT.132-160) | C (MOT.180L) | E | O | ØA | ØB | ØDint | ØJ |
---|---|---|---|---|---|---|---|
759 | 779 | 340 | 20x18º | 1365 | 1320 | 1263 | 15 |
MANUFACTURING FEATURES
• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.
MANUFACTURING FEATURES
• For axial (inlet and outlet) and centrifugal (inlet) fans.
UNDER REQUEST
• Versions in stainless 304 and stainless 316.
MANUFACTURING FEATURES
• Circular-circular coupling flange through anti-vibration canvas.
• Fire resistance M0: from -50ºC to +200ºC in continuous and 400ºC/2h
MANUFACTURING FEATURES
• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.
*Dial panel incorporated. Optional EMC filter.
Certifications: CE/UL/CSA/EN/GOST/CCC.
Protection index IP20.
The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.
SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
Switch for ATEX environments. Suitable for zones 1-2 (gas) and 21-22 (dust), index protection IP65. Manufactured in aluminum alloy and RAL 7000 gray finishing coat. External screws in stainless steel. Control on the front. Tensions up to 690V. According to directive 2014/34 / UE (ATEX).
MANUFACTURING FRATURES
• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.
UNDER REQUEST
• Stainless guard 304 or 316 with electro-polished finishing coat.
MANUFACTURING FEATURES
• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.