fan image
Model
CTH3 800 T6 7,5KW
Code
279800206

CTH3 800 T6 7,5KW

ROOF FAN, ABS COWL 400ºC/2h

MANUFACTURING FEATURES
• Roof cowl made of ABS
• Structure, roof base support and bird protection guard made of galvanised steel.
• High efficiency backward impeller with self-cleaning system of steel.
• Standard asynchronous motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230V 60Hz in single phase motors, 230/400V 60Hz  in three phase motors

APPLICATIONS
Specially designed for roof installation, they are suitable for:
• Smoke extraction.
• Smoke emergency exhaust with motor outside the hazardous area.
• Air renewal in buildings and industries.
• Industrial and professional kitchen hoods.
• Maximum continuous working temperature: carried air 80ºC, environment 60ºC for three phase and 50ºC for single phase motors.

UNDER REQUEST

• Sparking proof fan with EEx_d certified motor.

 

Fan

Max flow
32510 m³/h
Weight
205 Kg

Motor

Power
7,5 kW
RPM Motor
1158
I max. 400 V
15,2
I max. 690 V
8,81
Size
160L
Weight
95 Kg
Efficiency
91.4 %
FP
0.81
CTH3 800 T6 7,5KW
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

CTH3 800 T6 7,5KW

Dimensions scheme
A B aprox C D E F G H K aprox
1168,5 1205 1035 840 9 429,6 466 50 689

CTH3 800 T6 7,5KW

Electrical scheme

CTH3 800 T6 7,5KW

Model
INT 25 3P A
Code
INT253PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
INT 400 40A 3P
Code
508904001
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
SFC 400 III 16A *
Code
SFC400III16
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
BTI 1015
Code
A-508701015XX
Information
INCLINED ROOF FAN SUPPORT

MANUFACTURING FEATURES

• Inclined support for roof fans CTH3, ENKELROOF EEC, KENTALROOF CONFORT, and the resulting fans combining with the KIT TE and KIT TM

In the code, indicate the pitch instead of "XX"

UNDER REQUEST

• Specific inclination.

CTH3 800 T6 7,5KW

Spare parts scheme
Code Family Name Qty
1 R-279714479 ROOF COWL CTH3 710-800 x1
2 721001276 MOTOR 7,5kW T6 B5 400/690V x1
3 R-CTB-N802-42RD TURBINE Ø800 h=2 D42 RD x1
4 R-279801772 INLET-FRAME CTH3 800 x1