fan image
Model
CTH3 710 T6 4KW
Code
279710206

CTH3 710 T6 4KW

ROOF FAN, ABS COWL 400ºC/2h

MANUFACTURING FEATURES
• Roof cowl made of ABS
• Structure, roof base support and bird protection guard made of galvanised steel.
• High efficiency backward impeller with self-cleaning system of steel.
• Standard asynchronous motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230V 60Hz in single phase motors, 230/400V 60Hz  in three phase motors

APPLICATIONS
Specially designed for roof installation, they are suitable for:
• Smoke extraction.
• Smoke emergency exhaust with motor outside the hazardous area.
• Air renewal in buildings and industries.
• Industrial and professional kitchen hoods.
• Maximum continuous working temperature: carried air 80ºC, environment 60ºC for three phase and 50ºC for single phase motors.

UNDER REQUEST

• Sparking proof fan with EEx_d certified motor.

 

Fan

Max flow
22730 m³/h
Weight
170 Kg

Motor

Power
4 kW
RPM Motor
1152
I max. 230 V
16,5
I max. 400 V
9,46
Size
132M
Weight
68 Kg
Efficiency
89.3 %
FP
0.72
CTH3 710 T6 4KW
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

CTH3 710 T6 4KW

Dimensions scheme
A B aprox C D E F G H K aprox
1168,5 1118,5 1035 840 9 429,6 439,5 50 629

CTH3 710 T6 4KW

Electrical scheme

CTH3 710 T6 4KW

Model
INT 25 3P A
Code
INT253PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
INT 400 25A 3P
Code
508902501
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
KF 710-800
Code
960004660
Information
FIXING KIT FOR CTH3

MANUFACTURING FEATURES

• Fixing kit for CTH3 roof fan made of galvanized steel.

Model
KB 710-800
Code
960004560
Information
CTH3 TILTING KIT

MANUFACTURING FEATURES

• Tilting kit made of galvanised steel.
• It allows fan inclination to make cleaning of duct and impeller easier.

Model
KV CTH-3 710-800
Code
960004760
Information
CTH3 VERTICAL DISCHARGE

MANUFACTURING FEATURES

• Accessory to convert the CTH3 roof fan to vertical discharge.
• Manufactured in aluminuim

Model
SFC 400 III 12A *
Code
SFC400III12
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
BTI 1015
Code
A-508701015XX
Information
INCLINED ROOF FAN SUPPORT

MANUFACTURING FEATURES

• Inclined support for roof fans CTH3, ENKELROOF EEC, KENTALROOF CONFORT, and the resulting fans combining with the KIT TE and KIT TM

In the code, indicate the pitch instead of "XX"

UNDER REQUEST

• Specific inclination.

CTH3 710 T6 4KW

Spare parts scheme
Code Family Name Qty
1 R-279714479 ROOF COWL CTH3 710-800 x1
2 721001271 MOTOR 4KW T6 B5 230/400V x1
3 R-279719382 TURBINE THRE R63B2 710X224x38 RD x1
4 R-279711772 INLET-FRAME CTH3 710 x1