accessory image
Model
KIT-PE I 7A in: 230Vac II, out: 230Vac III
Code
KPEI04V2

KIT-PE

STAIRCASE OVERPRESSURE KIT

MANUFACTURING FEATURES

  • Automatic control of differential pressure and maintain it at 50Pa in a single stage according to the UNE-EN 12101-6 standard.
    • It consists of a control panel (KIT PE) and an air supply unit (any fan for air supply) that will provide the stairs or the escape route with enough pressure.
    • It is available for three-phase and single-phase equipment.
    • The KIT PE has everything necessary to operate autonomously, so the work of the installer will be much easier and it is only necessary connecting the kit to the fan and the fire detection control panel.

KIT PE is composed of the following elements:

  • Frequency inverter programmed at 50 Pa
    • Output frequency: 50Hz
    • High precision DPT differential pressure probe.
  • Steel frame fitted with a 3mm double bar lock to limit external access. IP66 protection. Complies with IEC 62208, UL, CUL, BV, DNV and GL standards.
    • Magneto-thermal protector
    • Line and error LED
    • Test pushbutton
    • Operation mode selector

 

The selection of the overpressure kits must be made based on the maximum absorbed intensity of the fan to be regulated.

Approx. weight
10.00 Kg
Max. I
'7 A

KIT-PE I 7A in: 230Vac II, out: 230Vac III

Dimensions scheme
A B C
300 400 210

KIT-PE I 7A in: 230Vac II, out: 230Vac III

Electrical scheme