Product out of catalogue
-HMTE
Model
HMTE 71 T6 0,75kW
Code
2697262640

HMTE 71 T6 0,75kW

AXIAL WITH FIBERGLASS COWL

MANUFACTURING FEATURES:

• Roof cowl made of reinforced fibreglass.
• Roof base support and bird protection guard with polyester powder coat finishing.
• Assembled on HM fans.(tubular)
• Variable pitch angle Polypropylene impeller (A2 profile) or polyamide impeller reinforced with fibreglass (other profiles).
• Squirrel cage asynchronous standard motor, IP-55 protection and rated class F insulation. Standard voltages 230V 50Hz for single phase motors, 230/400V 50Hz and for three phase motors up to 4kW and 400/690V 50Hz for higher powers.

APPLICATIONS:

Specially designed for roof installation, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction.
• Maximum working temperature: 1ph 50ºC, 3ph 60ºC.

AVAILABLE ON REQUEST

• B form impeller (air flow from impeller to motor)
• Reversible impeller 100%
• Cast aluminium impellers.
• 60Hz fans and special voltages.
• 2 speed motors.
• Hot dip galvanised and stainless steel housings.
• Galvanised steel sheet cowl.

Fan

Max flow
13060 m³/h
Weight
62 Kg

Motor

Power
0,75 kW
RPM Motor
925
I max. 230 V
3,39
I max. 400 V
1,95
Size
90L
Weight
19 Kg
Efficiency
78.9 %
FP
0.73
HMTE 71 T6 0,75kW
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

HMTE 71 T6 0,75kW

Dimensions scheme
A B C D E G H T
1010 350 610 50 715 1290 1100 840 14

HMTE 71 T6 0,75kW

Electrical scheme

HMTE 71 T6 0,75kW

Model
INT 25 3P A
Code
INT253PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
RP 71
Code
960340100
Information
PROTECTION GUARD FOR LONG CASE FANS

CONSTRUCTION FEATURES

• Protective grille on the motor and propeller side to prevent objects from entering. For HC and HCA models, the RP grille is only applicable on the propeller side. The RP is also suitable for the HMR EVO range, both for intake and discharge (note that the grille is of different sizes depending on whether it is for intake or discharge)
• Constructed with electro-welded rod.
• Compliant with ROHS directive 2002/95/EC.

ON REQUEST

• Grille in 304 or 316 stainless steel with electropolished finish.

Model
SFC 230 I 4,2A *
Code
SFC230I004
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
SFC 400 III 2,2A *
Code
SFC400III2
Information
FREQUENCY SPEED CONTROLLER

MANUFACTURING FEATURES

• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.

*Dial panel incorporated. Optional EMC filter.

Certifications: CE/UL/CSA/EN/GOST/CCC.

Protection index IP20.

The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current