fan image
Model
SYBILO 75N F300
Code
275750186

SYBILO 75N F300

CENTRIFUGAL JET FAN 300ºC/2h

MANUFACTURING FEATURES

Centrifugal powerful jet fan with low profile conceived for car parkings, working inside
the hazardous area and remove wide air volume in car parks 300ºC/2h.

FAN

• Galvanized steel sheet casing.
• Strong backward impeller with self-cleaning system made of strong galvanized steel sheet.
• External wiring box.
• Inlet protection.
• Feet included.

MOTOR

• Class H insulation, S1 continuous use and S2 emergency use, with bearing balls,
IP-55 protection, 2 speeds.
• 400V 4/8 poles Dalhander three phase motor.
• Maximum working temperature:
• S1 -> -20ºC +60ºC.
• S2 -> 300ºC / 2h.

Fan

Max flow
8280 m³/h
Weight
130 Kg

Motor

Power
2,2/0,37 kW
RPM Motor
1420/700
I max. 400 V
5,6/1,8
SYBILO 75N F300
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

SYBILO 75N F300

Dimensions scheme
A B C D E F H I K L Thrust (N)
1600 300 1000 351,5 1093 1052 800 250 13 4 75/19

SYBILO 75N F300

Electrical scheme

SYBILO 75N F300

Model
INT 400 25A 6P
Code
508902502
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
INT 25 6P A
Code
INT256PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
AVT (GENERIC)
Code
Information
CEILING ANTI-VIBRATION

MANUFACTURING FEATURES
Range designed for suspension of acoustic ceilings and machinery that requires a very high isolation level. These hangers are made of a high mechanical performance spring and incorporate a rubber bush conceived to avoid the acoustic bridges and the contact of a non aligned screw.
The metallic structure is very robust and it is supplied with an anti-corrosive zinc-plated coat.

APPLICATIONS
Support of Equipment for the support of gas or fluid pipes, air ducts and ventilation or air conditioning machinery.