fan image
Model
KIT TE + HM 71 T6 0,75kW (A2:6) 40º
Code
KTE71+26173462640P

KIT TE + HM 71 T6 0,75kW (A2:6) 40º

AXIAL WITH FIBERGLASS COWL

MANUFACTURING FEATURES:

• Roof cowl made of reinforced fibreglass.
• Roof base support and bird protection guard with polyester powder coat finishing.
• Assembled on HM fans.(tubular)
• Variable pitch angle Polypropylene impeller (A2 profile) or polyamide impeller reinforced with fibreglass (other profiles).
• Squirrel cage asynchronous standard motor, IP-55 protection and rated class F insulation. Standard voltages 230V 50Hz for single phase motors, 230/400V 50Hz and for three phase motors up to 4kW and 400/690V 50Hz for higher powers.

APPLICATIONS:

Specially designed for roof installation, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction.
• Maximum working temperature: 1ph 50ºC, 3ph 60ºC.

AVAILABLE ON REQUEST

• B form impeller (air flow from impeller to motor)
• Reversible impeller 100%
• Cast aluminium impellers.
• 60Hz fans and special voltages.
• 2 speed motors.
• Hot dip galvanised and stainless steel housings.
• Galvanised steel sheet cowl.

Fan

Max flow
12630 m³/h
Weight
61 Kg

Motor

Power
0,75 kW
RPM Motor
925
I max. 230 V
3,39
I max. 400 V
1,95
Size
90L
Weight
19 Kg
Efficiency
78.9 %
FP
0.73
KIT TE + HM 71 T6 0,75kW (A2:6) 40º
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

KIT TE + HM 71 T6 0,75kW (A2:6) 40º

Dimensions scheme
A B C D E F G H T
1010 350 610 50 715 1290 1100 840 14

KIT TE + HM 71 T6 0,75kW (A2:6) 40º

Electrical scheme

KIT TE + HM 71 T6 0,75kW (A2:6) 40º