LONG CASE FAN WITH BACKWARD IMPELLER
MANUFACTURING FEATURES:
• Reinforced fan casing manufactured in rolling steel sheet. Polyester powder finishing coat. Housing with motor access door.
• High efficiency backward impeller with self-cleaning system in steel sheet, balanced static and dynamically in origin.High efficiency impeller with built-in diffuser, which eliminates the need to use a scroll or spiral casing to obtain performance.
• Models with AC motor inside the air flow. Standard asynchronous squirrel cage motor with IP-55 protection and Class F insulation. Standard voltages of 230V50Hz for single phase motors, 230/400V50Hz & 400/690V 50Hz for three-phase 1 speed motors and 400V50Hz for 2 speed motors.
• Maximum working temperature 60ºC.
APPLICATIONS:
Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction.
A | B | C | D | F | G | H |
---|---|---|---|---|---|---|
1094.5 | 993.5 | 1019 | 708 | 1116 | 1070 | Ø12x16 |
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
CONSTRUCTION FEATURES
• Protective grille on the motor and propeller side to prevent objects from entering. For HC and HCA models, the RP grille is only applicable on the propeller side. The RP is also suitable for the HMR EVO range, both for intake and discharge (note that the grille is of different sizes depending on whether it is for intake or discharge)
• Constructed with electro-welded rod.
• Compliant with ROHS directive 2002/95/EC.
ON REQUEST
• Grille in 304 or 316 stainless steel with electropolished finish.
CONSTRUCTION FEATURES
• Protective grille on the motor and propeller side to prevent objects from entering. For HC and HCA models, the RP grille is only applicable on the propeller side. The RP is also suitable for the HMR EVO range, both for intake and discharge (note that the grille is of different sizes depending on whether it is for intake or discharge)
• Constructed with electro-welded rod.
• Compliant with ROHS directive 2002/95/EC.
ON REQUEST
• Grille in 304 or 316 stainless steel with electropolished finish.
MANUFACTURING FEATURES
• Made of steel and protected against corrosion with polyester resin powder.
MANUFACTURING FEATURES
• Specially designed for speed frequency control in ventilation applications.
• Ultra compact, simple operation and wide range of functions.
*Dial panel incorporated. Optional EMC filter.
Certifications: CE/UL/CSA/EN/GOST/CCC.
Protection index IP20.
The selection of SFC frequency drive speed controller must be made based on the maximum intensity absorbed by the fan to be regulated. The powers (kW) and the intensity for constant load refer to the normal duty (150% overload for 60 seconds). The intensity for quadratic load admits an overload of 110% during 60s.
SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current
Nº | Code | Family | Name | Qty |
---|---|---|---|---|
1 | 721001181 | MOTOR | 5,5kW T4 B3 400/690V | x1 |
2 | R-R63D1L630-38 | TURBINE | R63D1L630x180x38 LG | x1 |
3 | R-BAD630PK1 | INLET CONE | ED11P 630 | x1 |