fan image
Model
HCA EVO 50 EEC
Code
277509040AECV2

HCA EVO 50 EEC

SHORT CASE VARIABLE PITCH BLADES WITH EEC MOTOR

MANUFACTURING FEATURES
• Short case axial fan with reinforced body, with double flange, made of rolling steel sheet.
• Pad mounted motor support system with guide vanes.
• Polyester powder finishing coat.
• Low sound level and high performance.
• PM brushless motor (permanent magnets), synchronous, electronically commutated, high efficiency and low sound level. Specially designed for fans with electronic operation and control in deported box IP65.
    Working range: from 400 to 1200-2000rpm (depending on the models)
    Motor with IP54 protection and class F insulation. IP 65 drive case
    Power: 220V ± 10% single phase
    Power frequency: 50 / 60Hz
    Operating temperature range (electronical box): -20ºC to 50ºC
    Speed ​​control through signal 0-10V or PWM 
Cast aluminium impeller with variable pich angle (Stopped and in origin).

APPLICATIONS
Designed for inline installation, they are suitable for

• Air renewal in buildings and industries.
• Smoke extraction.
• Maximum transported air temperature: 50ºC.

 UNDER REQUEST
• Casing in hot galvanized sheet or stainless steel.

 

Fan

Max flow
10290 m³/h
Weight
37 Kg

Motor

Power
0,75 kW
RPM Motor
1500
I max. 230 V
5,8
HCA EVO 50 EEC
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

HCA EVO 50 EEC

Dimensions scheme
A B C D E F G
600 560 504 12x30 12 350 675

HCA EVO 50 EEC

Electrical scheme

HCA EVO 50 EEC

Model
INT 25 3P A
Code
INT253PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
RP 50
Code
960320100
Information
PROTECTION GUARD FOR LONG CASE FANS

CONSTRUCTION FEATURES

• Protective grille on the motor and propeller side to prevent objects from entering. For HC and HCA models, the RP grille is only applicable on the propeller side. The RP is also suitable for the HMR EVO range, both for intake and discharge (note that the grille is of different sizes depending on whether it is for intake or discharge)
• Constructed with electro-welded rod.
• Compliant with ROHS directive 2002/95/EC.

ON REQUEST

• Grille in 304 or 316 stainless steel with electropolished finish.

Model
PO 50
Code
960001656
Information
CASE FANS MOUNTING SUPPORT

MANUFACTURING FEATURES

• Made of steel and protected against corrosion with polyester resin powder.

Model
AC 500
Code
960003214
Information
CONECTION FLANGE

MANUFACTURING FEATURES

• For axial (inlet and outlet) and centrifugal (inlet) fans.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
BA-400 50
Code
960002064
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.

Model
REGC
Code
FX263300
Information
SPEED CONTROLLER FOR EEC MOTOR

MANUFACTURING FEATURES

• Speed remote controller for EEC motors.
• Adjusts the flow rate in a range from 0 to 100% at a maximum distance of 10m.
• It can be recessed or mounted on a wall. Can be installed outdoors.
• Working temperature from 0 to 40ºC.

Model
SIL-C 500/500
Code
960050050
Information
CIRCULAR SILENCER

MANUFACTURING FEATURES

• Valid for mounting in inlet and outlet according to the diameter of the corresponding pipe or adapted to the diameter of an optional flange. Consult to Casals Ventilación.
• Steel housing with thickness of 0.8mm for diameters up to 1250mm; and 1mm for higher diameters.
• Silencer flange with threaded inserts.
• Acoustic rock wool insulation of 70Kg/m3 with microperforated metal mesh that protects the fiberglass from erosion. Fire resistant insulation M0.
• Attenuation test carried out according to the ISO 7235 standard.
• Drills in accordance with Eurovent regulations.
• SIL-CN are equipped with an inner core that increases silencer attenuation.
• Maximum working temperature: 150ºC.
• Suitable for pressures up to 1000Pa

APPLICATIONS

• For attenuating the sound level of the fan.
• For coupling fans and circular pipes.

Other sizes, consult us.

Model
SIL-C 500/750
Code
960050075
Information
CIRCULAR SILENCER

MANUFACTURING FEATURES

• Valid for mounting in inlet and outlet according to the diameter of the corresponding pipe or adapted to the diameter of an optional flange. Consult to Casals Ventilación.
• Steel housing with thickness of 0.8mm for diameters up to 1250mm; and 1mm for higher diameters.
• Silencer flange with threaded inserts.
• Acoustic rock wool insulation of 70Kg/m3 with microperforated metal mesh that protects the fiberglass from erosion. Fire resistant insulation M0.
• Attenuation test carried out according to the ISO 7235 standard.
• Drills in accordance with Eurovent regulations.
• SIL-CN are equipped with an inner core that increases silencer attenuation.
• Maximum working temperature: 150ºC.
• Suitable for pressures up to 1000Pa

APPLICATIONS

• For attenuating the sound level of the fan.
• For coupling fans and circular pipes.

Other sizes, consult us.

Model
SIL-C 500/1000
Code
960050100
Information
CIRCULAR SILENCER

MANUFACTURING FEATURES

• Valid for mounting in inlet and outlet according to the diameter of the corresponding pipe or adapted to the diameter of an optional flange. Consult to Casals Ventilación.
• Steel housing with thickness of 0.8mm for diameters up to 1250mm; and 1mm for higher diameters.
• Silencer flange with threaded inserts.
• Acoustic rock wool insulation of 70Kg/m3 with microperforated metal mesh that protects the fiberglass from erosion. Fire resistant insulation M0.
• Attenuation test carried out according to the ISO 7235 standard.
• Drills in accordance with Eurovent regulations.
• SIL-CN are equipped with an inner core that increases silencer attenuation.
• Maximum working temperature: 150ºC.
• Suitable for pressures up to 1000Pa

APPLICATIONS

• For attenuating the sound level of the fan.
• For coupling fans and circular pipes.

Other sizes, consult us.

Model
SIL-CN 500/500
Code
961050050
Information
CIRCULAR SILENCER

MANUFACTURING FEATURES

• Valid for mounting in inlet and outlet according to the diameter of the corresponding pipe or adapted to the diameter of an optional flange. Consult to Casals Ventilación.
• Steel housing with thickness of 0.8mm for diameters up to 1250mm; and 1mm for higher diameters.
• Silencer flange with threaded inserts.
• Acoustic rock wool insulation of 70Kg/m3 with microperforated metal mesh that protects the fiberglass from erosion. Fire resistant insulation M0.
• Attenuation test carried out according to the ISO 7235 standard.
• Drills in accordance with Eurovent regulations.
• SIL-CN are equipped with an inner core that increases silencer attenuation.
• Maximum working temperature: 150ºC.
• Suitable for pressures up to 1000Pa

APPLICATIONS

• For attenuating the sound level of the fan.
• For coupling fans and circular pipes.

Other sizes, consult us.

Model
SIL-CN 500/750
Code
961050075
Information
CIRCULAR SILENCER

MANUFACTURING FEATURES

• Valid for mounting in inlet and outlet according to the diameter of the corresponding pipe or adapted to the diameter of an optional flange. Consult to Casals Ventilación.
• Steel housing with thickness of 0.8mm for diameters up to 1250mm; and 1mm for higher diameters.
• Silencer flange with threaded inserts.
• Acoustic rock wool insulation of 70Kg/m3 with microperforated metal mesh that protects the fiberglass from erosion. Fire resistant insulation M0.
• Attenuation test carried out according to the ISO 7235 standard.
• Drills in accordance with Eurovent regulations.
• SIL-CN are equipped with an inner core that increases silencer attenuation.
• Maximum working temperature: 150ºC.
• Suitable for pressures up to 1000Pa

APPLICATIONS

• For attenuating the sound level of the fan.
• For coupling fans and circular pipes.

Other sizes, consult us.

Model
SIL-CN 500/1000
Code
961050100
Information
CIRCULAR SILENCER

MANUFACTURING FEATURES

• Valid for mounting in inlet and outlet according to the diameter of the corresponding pipe or adapted to the diameter of an optional flange. Consult to Casals Ventilación.
• Steel housing with thickness of 0.8mm for diameters up to 1250mm; and 1mm for higher diameters.
• Silencer flange with threaded inserts.
• Acoustic rock wool insulation of 70Kg/m3 with microperforated metal mesh that protects the fiberglass from erosion. Fire resistant insulation M0.
• Attenuation test carried out according to the ISO 7235 standard.
• Drills in accordance with Eurovent regulations.
• SIL-CN are equipped with an inner core that increases silencer attenuation.
• Maximum working temperature: 150ºC.
• Suitable for pressures up to 1000Pa

APPLICATIONS

• For attenuating the sound level of the fan.
• For coupling fans and circular pipes.

Other sizes, consult us.

Model
BAD 13 (Ø500)
Code
960003463
Information
CIRCULAR-CIRCULAR ANTI-VIBRATION FLANGE

MANUFACTURING FEATURES

• Circular-circular coupling flange through anti-vibration canvas.
• Fire resistance M0: from -50ºC to +200ºC in continuous and 400ºC/2h

Model
KIT TE 50
Code
KTE50
Information
ROOF KIT FOR CASE FANS

Set that allows to install short or long case fans on the roof protecting them from inclement weather. Kit not suitable for fire (fiber cowl -20+110ºC).

MANUFACTURING FEATURES

Set consisting of:

• Cowl made of reinforced glass fiber protection cowl.
• Support framework for roof adaptation in laminated steel sheet protected against corrosion by powder coating polyester resin.
• Anti-bird protection grid protected against corrosion.

APPLICATIONS

Designed for roof installation, they are indicated for:
• Renovation of air in all types of buildings and industries.
• Smoke extraction.
• Contribution of clean air.
• Maximum temperature subject to installed fan.

The kit musn't be installed if the air speed is higher than 13m/s

UNDER REQUEST

• Framework support in AISI 304,316.
• Cold galvanized steel.
• Hot galvanized steel.

 

Model
KIT TM 50
Code
KTM50
Information
METALLIC ROOF KIT FOR CASE FANS

Set that allows to install short or long case fans on the roof protecting them from inclement weather. Kit suitable for fire (metal cap).

MANUFACTURING FEATURES

Set consisting of:
•Cowl made of galvanized sheet.
• Support framework for roof adaptation in laminated steel sheet protected against corrosion by powder coating polyester resin.
• Anti-bird protection grid protected against corrosion.

APPLICATIONS

Designed for roof installation, they are indicated for:
• Renovation of air in all types of buildings and industries.
• Smoke extraction.
• Contribution of clean air.
• Maximum temperature subject to installed fan.

UNDER REQUEST

• Framework support in AISI 304,316.
• Cold galvanized steel.
• Hot galvanized steel.

HCA EVO 50 EEC

Spare parts scheme
Code Family Name Qty
1 R-720331075IEC4V2 MOTOR EEC 750W (T.80) x1
2 R-H50006240AIMP IMPELLER 500:AA0:6 G40 D14 IMP x1
3 301002104R150 ELECTRONICAL DEVICE EEC750 1500RPM x1